NEC Article 700 Emergency System Requirements

Sources: 2023 National Electrical Code (NFPA 70) Articles 700, 701 and 702, and 2021 International Building Code (IBC) Chapter 27

Check your set instantly
Quick answer

NEC Article 700 covers emergency systems: legally required power for life safety loads such as egress lighting, exit signs and fire alarm. Power must arrive within 10 seconds of an outage, through transfer equipment that serves only emergency loads. Emergency wiring stays independent of other wiring, and its overcurrent devices are selectively coordinated.

The Pirros Quality Management System can check the transfer switches and emergency panels on every one-line diagram in your set and Revit model, instantly.

The manual way

How to check the code requirements

Article 700 is checked on the one-line diagram. The IBC decides which loads are emergency loads, and the NEC decides how they are switched, wired and protected. Check them in that order.

  • Start from the code analysis. The occupancy and height set the loads. Exit signs and egress lighting are emergency loads; elevators and smoke control are standby loads (IBC 2702.2). High-rises add more (IBC 403.4.8).
  • Sort the loads by article. Put emergency loads on their own panels, legally required standby loads on others and optional loads on a third set. Emergency circuits supply only emergency loads (NEC 700.15).
  • Give emergency loads their own transfer switch. Transfer equipment for emergency loads serves nothing else, so one generator feeding all three needs separate switches (NEC 700.5). Emergency power arrives within 10 seconds (NEC 700.12).
  • Route the feeders. Keep emergency wiring in its own raceways, cables and boxes (NEC 700.10(B)). In large assembly spaces and buildings over 75 feet, give feeders 2-hour protection or sprinklered routes (NEC 700.10(D)).
  • Coordinate the overcurrent devices. Emergency devices coordinate selectively with the supply side. A licensed professional engineer or other qualified person selects them and documents the selection (NEC 700.32).
  • Rate the generator room and sign the service. In a high-rise, a generator inside the building sits in a room of 2-hour fire barriers (IBC 403.4.8.1). A sign at the service equipment names each emergency source and where it is (NEC 700.7).

The IBC, not the NEC, sets egress lighting levels. Lighting on emergency power starts at an average of 1 footcandle at the floor, 0.1 minimum, for 90 minutes (IBC 1008.3, 2702.2.14). The occupancy group and height decide which loads are emergency loads, and the means of egress decides where exit signs and egress lighting go. Generator rooms use 2-hour fire-rated assemblies. The IBC rules are in Chapter 27 (ICC's free viewer); Article 700 is in NFPA 70 (NFPA). Pirros for MEP engineers covers families, standards and set review for electrical teams. On a drawing set these rules sit on the one-line diagram and riser, where an AI-powered quality management system reads them.

One-line diagram of a utility service and a generator feeding three transfer switches: the emergency system (Article 700) gets power within 10 seconds and serves egress lighting, exit signs and fire alarm through its own transfer switch, raceways, cables and boxes; legally required standby (Article 701) gets power within 60 seconds and serves elevators and smoke control; optional standby (Article 702) serves other loads; emergency feeders get 2-hour protection in assembly occupancies for 1,000 or more persons and buildings over 75 feet, emergency overcurrent devices are selectively coordinated and the selection documented, and load shedding keeps emergency loads first, then legally required standby, then optional standby
Pirros Quality Management

How Pirros checks the set

The Pirros Quality Management System reviews projects against code requirements, firm standards, and project specifications, then assigns, tracks, and resolves issues before they become RFIs or rework.

  • Reads every sheet in your set against the codes you pick for the project: the IBC, ADA and regional codes.
  • Every finding names the sheet, the location and the section behind it.
  • Findings are surfaced, never auto-applied. Your reviewer confirms, dismisses or escalates.

Requirements at a glance

NEC Article 700 Emergency System Requirements, by section
ElementRequirementSection
ScopeEmergency systems are legally required and classed as emergency by a governmental agency. They supply illumination, power or both automatically when the normal supply fails.NEC 700.1, 700.2
Articles 700, 701 and 702Emergency systems (700) protect life safety and get power within 10 seconds. Legally required standby systems (701) get it within 60 seconds. Optional standby systems (702) serve loads life safety doesn't depend on.NEC 700.12, 701.12, 702.1
Load transfer, IBCEmergency power within 10 seconds and standby power within 60 seconds of losing primary power. An emergency system is an acceptable alternative where a standby system is required.IBC 2702.1.4, 2702.1.7
DurationThe IBC requires 2 hours minimum without refueling or recharging, unless it says otherwise. The NEC sets the same 2-hour floor for the emergency source, except battery emergency lighting and unit equipment.IBC 2702.1.5 · NEC 700.12
Emergency loads, IBCExit signs and means of egress illumination, each powered for 90 minutes minimum.IBC 2702.2.6, 2702.2.14
Standby loads, IBCElevators and platform lifts, smoke control systems and emergency voice/alarm systems. Emergency responder radio coverage runs 12 hours at full capacity.IBC 2702.2.2, 2702.2.3, 2702.2.4, 2702.2.17
High-rise loadsEmergency: exit signs and egress lighting, elevator car lighting, emergency voice/alarm, fire detection, fire alarm, electric fire pumps and the fire command center. Standby: smokeproof enclosure ventilation and detection, and elevators.IBC 403.4.8.3, 403.4.8.4
Generator room, high-riseA generator inside the building sits in a room enclosed by 2-hour fire barriers or horizontal assemblies. Manual start and transfer are supervised from the fire command center.IBC 403.4.8.1
Installation and testingInstalled to the IFC, NFPA 70, NFPA 110 and NFPA 111. The authority having jurisdiction conducts or witnesses an acceptance test, and periodic tests are recorded in writing.IBC 2702.1.3 · NEC 700.3
Temporary sourceA system with a single alternate source has a permanent means to connect a temporary source during maintenance or repair.NEC 700.3(F)
Capacity and load sheddingThe source carries all emergency loads that run at once. Where it also serves other loads, automatic load shedding keeps priority: emergency, then legally required standby, then optional standby.NEC 700.4
Transfer equipmentAutomatic, listed for emergency use, and supplying only emergency loads. One generator serving emergency and other loads needs separate transfer switches.NEC 700.5
Signals and signsAudible and visual signals for derangement of the source, the source carrying load, battery charger failure and ground faults. A sign at the service equipment gives the type and location of each on-site emergency source.NEC 700.6, 700.7
Wiring kept independentEmergency wiring shares no raceway, cable, box or cabinet with other wiring. The exceptions include transfer equipment, luminaires fed from two sources and a few other listed cases.NEC 700.10(B)
Feeder fire protectionApplies in assembly occupancies for 1,000 or more persons and in buildings over 75 feet high. Feeders run in fully sprinklered spaces, a 2-hour listed cable or circuit protective system, a 2-hour assembly, or 2 inches of concrete. Feeder equipment sits in sprinklered spaces or 2-hour rooms.NEC 700.10(D)
Branch circuits and lightingEmergency circuits supply only emergency loads and are never part of a multiwire branch circuit. One failed lamp can't leave a space in total darkness. An indoor service disconnect gets emergency lighting.NEC 700.15, 700.16(B), 700.16(D), 700.19
Selective coordinationEmergency overcurrent devices coordinate selectively with all supply-side devices. A licensed professional engineer or other qualified person selects them, and the selection is documented and kept available.NEC 700.32

These rules are from the 2023 NEC (NFPA 70) and the 2021 IBC; check the editions and amendments your jurisdiction enforces. Subsection numbers in Article 700 have moved between NEC editions, so cite the edition on your project. Health care facilities follow Article 517 and NFPA 99 for their essential electrical systems.

FAQ

Frequently asked questions.

Can't find what you're looking for?
Get in touch.

Emergency systems: those legally required and classed as emergency by a governmental agency (NEC 700.1, 700.2). They supply power, lighting or both automatically when normal power fails. Typical loads are egress lighting, exit signs and fire alarm, powered within 10 seconds.

Article 700 covers emergency systems for life safety, with power within 10 seconds. Article 701 covers legally required standby systems, with power within 60 seconds. Article 702 covers optional standby systems, where life safety doesn't depend on them.

Exit signs and means of egress illumination, each for 90 minutes (IBC 2702.2.6, 2702.2.14). In a high-rise the list adds elevator car lighting, emergency voice/alarm, fire detection, fire alarm, electric fire pumps and the fire command center (IBC 403.4.8.4).

No. Emergency wiring stays in its own raceways, cables, boxes and cabinets (NEC 700.10(B)). The exceptions include transfer equipment and luminaires fed from two sources. Emergency circuits supply only emergency loads (NEC 700.15).

No. Transfer equipment for emergency loads supplies only emergency loads (NEC 700.5). A generator serving emergency, legally required standby and optional loads needs separate transfer switches. Load shedding keeps the emergency loads first (NEC 700.4).

In assembly occupancies for 1,000 or more persons and in buildings over 75 feet high (NEC 700.10(D)). Feeders then run in fully sprinklered spaces, a 2-hour listed cable or circuit protective system, a 2-hour assembly, or 2 inches of concrete.

A design aid, not legal advice. Confirm requirements with the authority having jurisdiction.

Talk to a product specialist about Pirros.

Set up a time with our team and see Pirros for yourself.

By submitting, you agree to our Privacy Policy and Terms of Service.