Fire Compartmentation: Where Compartment Walls and Floors Are Required

Sources: Approved Document B (fire safety), Volumes 1 and 2, 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments (requirement B3)

Check your set instantly
Quick answer

Under Approved Document B, walls between buildings and between different uses are compartment walls. Every floor in blocks of flats is a compartment floor, except within a flat. Non-residential storeys stay within Table 8.1, such as 2,000 m² for an unsprinklered shop. Compartment walls run to the floor or roof above, with fire resistance from Tables B1 and B2.

The Pirros Quality Management System can check every compartment wall, compartment floor and wall head on your fire strategy plans and sections in your set and Revit model, instantly.

The manual way

How to check the code requirements

Compartment lines start on the fire strategy plan and are proven on the sections. Check where each line must go, then how it meets floors, roofs and other walls, then what passes through it.

  • Draw the compartment lines. Mark walls between buildings and between different uses, and the floors that must be compartment floors (Vol 2 8.2 to 8.11, Vol 1 7.1). Tag each with its fire resistance.
  • Check each storey against Table 8.1. Measure each compartment on a non-residential storey. An unsprinklered shop storey over 2,000 m² needs a compartment wall, or a sprinkler system.
  • Follow each wall up the section. Run compartment walls to the underside of the floor or roof above, not to a suspended ceiling (8.20, 9.4). Walls between buildings run full height in one plane (8.18).
  • Detail the head and junctions. Show a head detail that copes with deflection, 40 mm in the middle half of a span unless assessed lower (8.24). Fire-stop the junctions with external walls (8.22).
  • Check the roof junction. Show the 1,500 mm BROOF(t4) zone each side of the wall (8.26). Or take the wall through the roof: 375 mm, or 200 mm where 8.29 allows.
  • List every opening. Check each door, duct and pipe against 8.30 and 8.31, and fire-stop the gaps (Section 10). Stairs and lifts that cross compartments go in protected shafts (8.32).

In the US, the nearest equivalents are fire walls and fire barriers, under different rules. The UK rules are in Section 8 of Approved Document B Volume 2 and Section 7 of Volume 1. In Revit, view filters can colour the fire-rated walls on plan. On a drawing set the lines sit on fire strategy plans and sections, which is where an AI-powered quality management system reads them.

Section through a three-storey shop and the building next door: the wall between them runs full height in one plane through the roof space, with 1,500 mm of BROOF(t4) roof each side; compartment floors fire-stopped where they meet the external wall; an internal compartment wall taken up to the slab above, beside one wrongly stopped at a suspended ceiling with a cavity barrier over it; a protected stair; an unsprinklered shop kept to 2,000 m² per storey
Pirros Quality Management

How Pirros checks the set

The Pirros Quality Management System reviews projects against code requirements, firm standards, and project specifications, then assigns, tracks, and resolves issues before they become RFIs or rework.

  • Reads every sheet in your set against the codes you pick for the project: the Building Regulations and Approved Documents.
  • Every finding names the sheet, the location and the section behind it.
  • Findings are surfaced, never auto-applied. Your reviewer confirms, dismisses or escalates.

Requirements at a glance

Fire Compartmentation: Where Compartment Walls and Floors Are Required, by section
ElementRequirementSection
Legal requirementA wall common to two buildings resists fire spread between them; each terraced or semi-detached house counts as a separate building. Where reasonably necessary, the building is sub-divided with fire-resisting construction, automatic fire suppression, or both.Requirement B3(2), B3(3)
All buildingsA wall common to two or more buildings is a compartment wall. Parts used mainly for different purposes are separated, unless one use is ancillary. The lowest floor need not be a compartment floor.Vol 2 paras 8.2, 8.3, 8.5
FlatsEvery floor, except one within a flat. Every wall separating a flat from the rest of the building, walls enclosing a refuse store, and walls common to two buildings.Vol 1 para 7.1
HousesWalls between semi-detached and terraced houses are compartment walls, 60 minutes minimum. An integral garage is separated by REI 30 construction.Vol 1 paras 5.5, 5.6, Table B2
Residential buildingsEvery floor is a compartment floor in 'residential (institutional)' and 'residential (other)' buildings, such as hospitals, care homes and hotels.Vol 2 paras 8.8, 8.10
Non-residential buildingsWalls needed to keep within Table 8.1. Every floor if the top storey is more than 30 m above ground. The ground floor over a basement, and every basement floor but the lowest where a basement is more than 10 m deep.Vol 2 para 8.11
Separate occupanciesIn shop and commercial, industrial and storage buildings, every wall or floor between separate occupancies.Vol 2 para 8.11e
Maximum compartment sizeOffices: no limit. Unsprinklered shops: 2,000 m² per storey. Other unsprinklered assembly and commercial buildings: 2,000 m² per storey if multi-storey. With sprinklers, their multi-storey limit is 4,000 m².Vol 2 Table 8.1
SprinklersThroughout blocks of flats with a top storey more than 11 m above ground. In office, shop, assembly, industrial and storage buildings with a top storey above 30 m, except light-vehicle car parks.Vol 1 para 7.4 · Vol 2 para 8.14
Fire resistanceWalls separating a flat or separate occupancies: REI 60 or Table B2, whichever is less. Other compartment walls and floors: Table B2, by purpose group and height.Vol 2 Table B1 items 3, 6, 7, Table B2
Walls between buildingsRun the full height of the building in one continuous vertical plane, and continue through any roof space to the underside of the roof.Vol 2 para 8.18 · Vol 1 para 7.8
Other compartment wallsRun the full height of the storey, and through the roof space in a top storey. Cavity barriers above a ceiling cannot complete the line.Vol 2 paras 8.20, 8.21, 9.4
Junctions and wall headsFire-stop junctions with other compartment walls and external walls. The head allows for floor deflection in a fire, assumed to be 40 mm in the middle half of a span.Vol 2 paras 8.22, 8.24
Roof junctionMeet the underside of the roof covering, fire-stopped, and continue across any eaves. Give the roof a 1,500 mm BROOF(t4) zone each side on an A2-s3, d2 deck, or take the wall through it.Vol 2 paras 8.25, 8.26, 8.29
Openings and protected shaftsIn walls between buildings or occupancies, only an escape fire doorset matching the wall, and pipes. Stairs, lifts, chutes, ducts and pipes between compartments go in protected shafts, whose walls count as compartment walls.Vol 2 paras 8.30, 8.31, 8.32

These rules are from Approved Document B, 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments, for England. From 2 September 2029, the national BS 476 fire resistance classes are withdrawn, leaving European classes or an assessment. Once a building is in use, its fire precautions fall under the Regulatory Reform (Fire Safety) Order 2005 and its fire risk assessment. Wales and Scotland set their own rules.

FAQ

Frequently asked questions.

Can't find what you're looking for?
Get in touch.

Dividing a building into compartments with fire-resisting walls and floors, to inhibit the spread of fire within it. Approved Document B sets where compartment walls and floors go and how long they resist fire. Requirement B3 of the Building Regulations 2010 is the legal basis.

Yes. Requirement B3 asks for sub-division with fire-resisting construction where reasonably necessary, and for walls between buildings that resist fire spread. Approved Document B shows one way to comply. Once the building is in use, the Regulatory Reform (Fire Safety) Order 2005 applies.

Walls between buildings and between different main uses, in every building (Vol 2 8.2, 8.3). Every floor in flats, except within a flat, and in hotels, hospitals and care homes. Non-residential buildings add walls to meet Table 8.1, and floors where the top storey exceeds 30 m.

In non-residential buildings, Table 8.1 sets the limit. Offices have none. An unsprinklered shop storey is 2,000 m² at most, and sprinklers raise multi-storey limits to 4,000 m². In an unsprinklered multi-storey industrial building, storeys can reach 7,000 m² where the top storey is up to 18 m.

In a wall between buildings or occupancies, only an escape fire doorset matching the wall, and pipes (8.30). Other compartment walls and floors can also take services, A1 refuse chutes, atria to BS 9999 and protected shafts (8.31). Every gap around them is fire-stopped (Section 10).

Compartmentation is the fire-resisting walls and floors themselves. Fire-stopping seals every joint, imperfect fit and service opening through them, so their fire resistance is not impaired (10.1). Cavity barriers are different again: they close and divide concealed spaces (Section 9).

A design aid, not legal advice. Confirm requirements with Building Control.

Contains public sector information licensed under the Open Government Licence v3.0.