Exit Access Travel Distance Limits

Sources: 2021 International Building Code (IBC) Section 1017

Check your set instantly
Quick answer

Exit access travel distance runs from the most remote point of a space to the entrance to the nearest exit. Groups A, E, F-1, M, R and S-1 get 200 feet without sprinklers and 250 feet with them. Sprinklered to NFPA 13, Group B gets 300 feet and F-2, S-2 and U get 400 feet.

The Pirros Quality Management System can check the travel distances on every life safety plan in your set and Revit model, instantly.

The manual way

How to check the code requirements

Travel distance is checked on the life safety plan, from the farthest point of each space to the nearest exit. The limit comes from the occupancy group and the sprinkler standard on the code sheet.

  • Find the limit for each floor. Read the occupancy group and sprinkler standard off the code sheet, then the limit from Table 1017.2. A Group M first floor and Group B floors above, sprinklered to NFPA 13, get 250 and 300 feet.
  • Start at the most remote point. Begin in the far corner of each room, area or space, not at its door (IBC 1017.3).
  • Follow the natural path. Draw the route a person would actually walk, along the natural and unobstructed path. Dimension each segment and label the total.
  • Stop at the entrance to the exit. The measurement ends at the door to an enclosed exit stair or at an exterior exit door. Where two exits are required, measure to the nearer one.
  • Count open stairs. An exit access stair that isn't enclosed is part of the path. Measure it along the nosings at the center of the stair and its landings (IBC 1017.3.1).
  • Check single-exit stories separately. A story served by one exit uses the lower limits in Tables 1006.3.4(1) and 1006.3.4(2).

Travel distance is one of the limits on a means of egress layout, alongside the common path of egress travel and dead-end corridors. The occupancy group and the sprinkler system recorded in the code analysis decide which limit applies. The route to an area of refuge is held to the same limit (IBC 1009.6.1). The IBC requirements are in Section 1017 (ICC's free viewer). On a drawing set they sit on the life safety plans, which is where an AI-powered quality management system reads them.

Plan of a Group B office floor sprinklered to NFPA 13, with exit stairs at opposite ends: the travel path starts at the most remote corner of an office, runs through its door and along the corridor, and stops at the door to the nearer exit stair, its segments a plus b totaling 300 feet maximum, or 200 feet without sprinklers. A section through an open exit access stair shows the path measured along the nosings, which counts, and stopping at the door to an enclosed exit stair, inside which travel is not counted
Pirros Quality Management

How Pirros checks the set

The Pirros Quality Management System reviews projects against code requirements, firm standards, and project specifications, then assigns, tracks, and resolves issues before they become RFIs or rework.

  • Reads every sheet in your set against the codes you pick for the project: the IBC, ADA and regional codes.
  • Every finding names the sheet, the location and the section behind it.
  • Findings are surfaced, never auto-applied. Your reviewer confirms, dismisses or escalates.

Requirements at a glance

Exit Access Travel Distance Limits, by section
ElementRequirementSection
MeasurementFrom the most remote point of each room, area or space, along the natural and unobstructed path, to the entrance to an exit. Where more than one exit is required, to the nearest one.IBC 1017.3
Groups A, E, F-1, M, R, S-1200 feet without sprinklers. 250 feet with an NFPA 13 or NFPA 13R system throughout.IBC Table 1017.2
Group B200 feet without sprinklers. 300 feet with an NFPA 13 system throughout.IBC Table 1017.2
Groups F-2, S-2, U300 feet without sprinklers. 400 feet with an NFPA 13 system throughout.IBC Table 1017.2
Group I-4150 feet without sprinklers. 200 feet with an NFPA 13 system throughout.IBC Table 1017.2
Groups I-1, I-2, I-3Not permitted without sprinklers. 250 feet for I-1 with NFPA 13 or 13R; 200 feet for I-2 and I-3 with NFPA 13.IBC Table 1017.2
Group HNot permitted without sprinklers. Sprinklered under Section 903.2.5.1: 75 feet for H-1, 100 for H-2, 150 for H-3 and 175 for H-4. H-5: 200 feet with NFPA 13.IBC Table 1017.2
Groups R-3 and R-4 with NFPA 13DWhere an NFPA 13D system is permitted, Section 1006.2.2.6 limits Group R-3 to 125 feet and Group R-4 to 75 feet.IBC 1006.2.2.6
Exterior egress balconyUp to 100 feet more where the last part of the exit access is an exterior egress balcony at least as long as the increase.IBC 1017.2.1
One-story F-1 and S-1400 feet where the F-1 or S-1 part is one story, with at least 24 feet from floor to ceiling or deck. The building needs NFPA 13 throughout.IBC 1017.2.2
Stairs and rampsExit access stairways and ramps count. Stairs are measured on a plane tangent to the nosings at the center of the stair and landings. Ramps are measured on the walking surface at the center.IBC 1017.3.1
Measurement exceptionsIn open parking garages, measure to the closest riser of an exit access stairway or slope of an exit access ramp. Smoke-protected and open-air assembly seating follows Section 1030.7.IBC 1017.3
AtriumsWhere the path runs through an atrium at a level other than exit discharge, the part inside the atrium is 200 feet maximum. Otherwise Table 1017.2 applies.IBC 1017.3.2
Single-exit storiesA story with one exit has lower limits, mostly 75 feet, with occupant caps by group. Groups B, F and S get 100 feet with NFPA 13. Group R-2 stories with up to four dwelling units get 125 feet.IBC Table 1006.3.4(1), 1006.3.4(2)
Refrigeration roomsRefrigeration machinery rooms: every point within 150 feet of an exit or exit access doorway. Unsprinklered refrigerated rooms over 1,000 square feet kept below 68°F: also 150 feet.IBC 1006.2.2.2, 1006.2.2.3
Other modificationsMalls, Groups I-2 and I-3, special amusement areas, aircraft manufacturing, temporary structures and pedestrian walkways have their own limits, listed in the table's note a.IBC Table 1017.2 note a

These numbers are from the 2021 IBC; check the edition and amendments your jurisdiction enforces. The 2024 IBC keeps the same values in Table 1017.2. The sprinklered values need the system named in each row: NFPA 13 for some groups, NFPA 13 or 13R for others.

FAQ

Frequently asked questions.

Can't find what you're looking for?
Get in touch.

The distance a person walks from the most remote point of a room, area or space to the entrance to an exit (IBC 1017.3). It covers the exit access, the part of the means of egress before the exit. Travel inside an enclosed exit stair isn't counted.

It depends on the occupancy group and sprinklers (IBC Table 1017.2). Without sprinklers, most groups get 200 feet and F-2, S-2 and U get 300 feet. The minimum distance between two exits is a separate rule (IBC 1007.1.1).

250 feet for Groups A, E, F-1, M, R, S-1 and I-1, with NFPA 13 or 13R. With NFPA 13, 300 feet for Group B and 400 feet for F-2, S-2 and U (IBC Table 1017.2). One-story F-1 and S-1 buildings with 24-foot ceilings get 400 feet (IBC 1017.2.2).

From the most remote point of each space, along the natural and unobstructed path, to the entrance to the nearest exit (IBC 1017.3). Dimension each segment of the route on the life safety plan and add them up.

Exit access stairs and ramps count, measured along the nosings or walking surface at the center (IBC 1017.3.1). An enclosed exit stair is the exit itself, so the measurement stops at its door.

The common path is the first part of the travel distance. It ends where occupants can reach two exits by separate routes (IBC 202). Its limits are much lower, set in Table 1006.2.1. Travel distance continues on to the nearest exit.

A design aid, not legal advice. Confirm requirements with the authority having jurisdiction.