ADA Signage Height and Location Requirements

Sources: 2010 ADA Standards for Accessible Design, 2021 International Building Code (IBC) and ICC A117.1-2017

Check your set instantly
Quick answer

Signs naming permanent rooms, and signs at exit doors, need raised characters and braille. Mount them 48 to 60 inches above the floor, measured to the baselines of the tactile characters, on the latch side of the door. Keep an 18 by 18-inch clear floor space centered on the sign, beyond the door swing.

The Pirros Quality Management System can check the height of every tactile sign on your door elevations in your set and Revit model, instantly.

The manual way

How to check the code requirements

A tactile sign gets placed twice: in elevation for its height, and in plan for its side of the door and its clear floor space. Check both at every door that names a room.

  • List the tactile signs. Room and space names, toilet rooms and exit doors get raised characters and braille. Directional and informational signs get visual characters only (216). Put the split in the signage schedule.
  • Set the height on the door elevation. Dimension 48 inches minimum to the baseline of the lowest tactile character, usually the braille. Keep the baseline of the highest raised character at 60 inches maximum (703.4.1).
  • Put the sign on the latch side. At double doors with one active leaf, use the inactive leaf. With two active leaves, use the wall to the right of the right-hand door (703.4.2).
  • Check the clear floor space in plan. Draw an 18 by 18-inch square centered on the sign, clear of the door's swing from closed to 45 degrees open (703.4.2).
  • Check the characters on the shop drawings. Raised characters 5/8 to 2 inches high, uppercase and sans serif. Grade 2 braille sits below the text, 3/8 inch minimum from it (703.2, 703.3).
  • Watch overhead and post-mounted signs. Overhead signs keep 80 inches of headroom. Signs on posts overhang 12 inches at most between 27 and 80 inches up (307.3, 307.4).

The sign's clear floor space sits beside the door maneuvering clearance, and area of refuge signs and accessible parking signs have rules of their own. Toilet rooms follow the ADA bathroom requirements, and tactile exit signs mark the doors to the exit stairways. A signage schedule in Revit puts every sign in one list. The Access Board explains these rules in its guide to signs. On a drawing set sign heights sit on the door elevations, which is where an AI-powered quality management system reads them.

Door elevation, sign detail and plans of a tactile room sign on the latch side of the door: 48 inches minimum from the floor to the braille baseline and 60 inches maximum to the baseline of the highest raised character; raised characters 5/8 to 2 inches high, with Grade 2 braille 3/8 inch minimum below them; an 18 by 18-inch clear floor space centered on the sign, beyond the door's swing from closed to 45 degrees open; and, at double doors, the sign on the inactive leaf when one leaf is active, or to the right of the right-hand door when both are.
Pirros Quality Management

How Pirros checks the set

The Pirros Quality Management System reviews projects against code requirements, firm standards, and project specifications, then assigns, tracks, and resolves issues before they become RFIs or rework.

  • Reads every sheet in your set against the codes you pick for the project: the IBC, ADA and regional codes.
  • Every finding names the sheet, the location and the section behind it.
  • Findings are surfaced, never auto-applied. Your reviewer confirms, dismisses or escalates.

Requirements at a glance

ADA Signage Height and Location Requirements, by section
ElementRequirementSection
Which signs complySigns provided under 216 comply with 703. Exempt: building directories, menus, seat and row designations, occupant names, building addresses, company names and logos, and temporary signs posted 7 days or less.ADA 216.1
Permanent rooms and spacesVisual and tactile: raised characters with braille. Exterior signs that are not at the door to the space they serve need not be tactile.ADA 216.2
PictogramsWhere a pictogram identifies a permanent room, its field is 6 inches high minimum, with tactile text descriptors directly below it.ADA 703.6.1, 703.6.3
Directional and informational signsVisual characters only.ADA 216.3 · 703.5
Exit doorsDoors at exit passageways, exit discharge and exit stairways get tactile signs. The IBC asks for EXIT in visual characters, raised characters and braille beside those doors.ADA 216.4.1 · IBC 1013.4
Visual and tactile on one signOne sign may carry both, or two separate signs may: one visual, one tactile.ADA 703.1
Raised charactersRaised 1/32 inch minimum, uppercase, sans serif. 5/8 to 2 inches high, based on the uppercase I; ½ inch minimum where separate visual characters carry the same information.ADA 703.2.1, 703.2.2, 703.2.3, 703.2.5
BrailleContracted (Grade 2), below the text and below all lines of multi-line text. 3/8 inch minimum from other tactile characters and from raised borders.ADA 703.3, 703.3.2
Mounting height48 inches minimum to the baseline of the lowest tactile character, and 60 inches maximum to the baseline of the highest. Elevator car controls are exempt.ADA 703.4.1
Location at a doorAlongside the door on the latch side. At double doors with one active leaf, on the inactive leaf; with two active leaves, to the right of the right-hand door. With no wall space there, on the nearest adjacent wall.ADA 703.4.2
Clear floor space at the sign18 by 18 inches minimum, centered on the tactile characters, beyond the arc of any door swing between closed and 45 degrees open.ADA 703.4.2
Sign on the doorAllowed on the push side of a door with a closer and no hold-open device.ADA 703.4.2 Exception
Visual characters40 inches minimum above the floor. Their minimum height depends on mounting height and viewing distance: 5/8 inch for signs 40 to 70 inches high, read from under 72 inches. Non-glare, contrasting with the background.ADA 703.5.6, Table 703.5.5, 703.5.1
International Symbol of Accessibility (ADA)At accessible entrances where not all comply, existing toilet rooms where not all comply, accessible parking spaces and accessible check-out aisles.ADA 216.6, 216.8, 216.5, 216.11
IBC signsThe ISA also marks passenger loading zones, dressing rooms, areas of refuge, exterior areas for assisted rescue and recreational lockers. Toilet room signs are tactile. Directional signs with the ISA point the way from inaccessible entrances, toilet rooms and elevators.IBC 1112.1, 1112.2, 1112.3
Overhead and post-mounted signs80 inches minimum headroom. Signs on posts or pylons overhang 12 inches maximum where they sit 27 to 80 inches above the floor.ADA 307.4, 307.3

These numbers are from the 2010 ADA Standards and the 2021 IBC; check the edition and amendments your jurisdiction enforces. The 2021 and 2024 IBC reference ICC A117.1-2017, which keeps the 48 to 60-inch band and the latch-side rule (703.3.10, 703.3.11). It measures the band separately for raised characters and for braille (703.4.5).

FAQ

Frequently asked questions.

Can't find what you're looking for?
Get in touch.

Signs naming permanent rooms and spaces, such as room numbers and restroom signs (ADA 216.2). Also signs at the doors to exit stairways, exit passageways and exit discharge (216.4.1). Directional and informational signs need visual characters only (216.3).

At least 48 inches to the baseline of the lowest tactile character, and at most 60 inches to the baseline of the highest (ADA 703.4.1). Both are measured from the floor. The lowest tactile character is usually the braille.

The latch side, alongside the door (ADA 703.4.2). Leave an 18 by 18-inch clear floor space centered on the sign, beyond the arc of the door swing from closed to 45 degrees open.

With one active leaf, on the inactive leaf. With two active leaves, to the right of the right-hand door. Where there is no wall space, on the nearest adjacent wall (ADA 703.4.2).

Only on the push side of a door with a closer and no hold-open device (ADA 703.4.2, Exception). Otherwise it goes beside the door on the latch side, or on the inactive leaf of a pair with one active leaf.

The tactile sign at the exit door does. Doors to exit stairways, exit passageways and exit discharge get raised characters and braille (ADA 216.4.1). The IBC asks for the word EXIT in visual characters, raised characters and braille (1013.4).

A design aid, not legal advice. Confirm requirements with the authority having jurisdiction.